| |
| Case Studies : Troubleshooting |
|
During the operation of a plant
or after a revamp, the plant sometimes under-performs for reasons that are not
immediately apparent. In such circumstances it is necessary to carefully
investigate the problem, go beyond the obvious cause and find the real reason
for the problem.
During a distillation column revamp for about a 30% capacity increase,
it was decided that the existing air-cooled exchanger would still be adequate
for the new duty. After start-up it was found that the column temperature and
pressure could not be controlled and continuous venting was required. The
immediate solution required by the plant operator was that a new larger cooler
be installed. Purchase and installation of a new cooler would have added
considerable cost and delay to the project.
The calculations showed that the cooler size was adequate. After this
was confirmed with a cooler supplier, it was realised that the problem was
caused by something else. Careful observation of the operation, together with a
detailed review of piping and control valves showed that the system as
originally designed was impossible to vent. It was suspected that the top row
of tubes was completely inert blanketed and the only reason the problem did not
cause concern before the revamp was that there was sufficient excess cooler
surface to compensate for the blanketed tubes.
An infrared remote temperature sensor was used to measure approximate
tube temperatures at various locations in the cooler tube bundle. These
measurements confirmed the probability that the top tubes were not performing
any heat transfer.
A small piping jump-over was installed to allow inert venting from the
exchanger. After start-up the exchanger performed as per design and the column
could be controlled at the correct temperature and pressure. Not only was the
eventual solution cheaper and quicker than the first proposal, but the new
cooler would not have solved the problem.
| A case
study from AVEC adding value through innovation |